The PanelView Plus 6 terminal, catalog number 2711P-K6M5A, is part of Rockwell Automation's PanelView Plus series, designed for graphical monitoring, control, and display applications. It is a rugged terminal that integrates well with the Integrated Architecture platform, offering a range of features for scalable and reliable performance. The terminal is designed to provide real-time monitoring of its displays via a web browser, making it suitable for applications that require remote monitoring and control.
Technical Specifications
- Environmental Specifications: The terminal operates in temperatures ranging from 0°C to 55°C (32°F to 131°F) and is resistant to 90% noncondensing humidity. It can withstand vibrations of 10-57 Hz with a 0.012 peak-to-peak displacement and shock of 15 G at 11 ms for operating conditions and 30 G at 11 ms for non-operating conditions.
- Display and User Interface: The terminal features a 4.5-inch by 3.4-inch display area with a stainless steel membrane keypad that supports numeric, navigation, and function keys. The keypad can withstand 1 million presses and has an operating force of 340 g.
- Power and Battery: The terminal operates on an input voltage of 100-240V AC, 50-60 Hz, and includes a battery-backed clock for real-time clock functionality. The battery life is at least four years at 25°C (77°F), and it is field-replaceable with a CR2032 coin-cell lithium battery.
- Communication and Connectivity: The terminal includes one USB host port for connecting a USB mouse, keyboard, printer, or USB flash drives, as well as one USB device port for connecting a host personal computer. It also supports Ethernet (10/100 Mbps, auto-MDI/MDI-X) and RS-232 communication ports.
- Software: The terminal runs on FactoryTalk View Machine Edition software, version 6.10 or later, which supports real-time monitoring and control, as well as data logging and file transfer capabilities.
Documentation and Resources
- User Manual: The user manual for this product is catalog number 2711P-UM001.
- Technical Data: The technical data for this product is catalog number 2711P-TD005.
- Catalog Number Conversions: The catalog number conversion table (Table 13) in the document "PanelView Plus to PanelView Plus 6 Catalog Number Conversions" provides information on how to select a new generation PanelView Plus 6 terminal replacement for existing PanelView Plus terminals.
Installation and Troubleshooting
- Installation: The installation process for the PanelView Plus 6 terminal involves mounting the terminal in a suitable location, connecting it to power and communication cables, and configuring the software according to the specific application requirements.
- Troubleshooting: Troubleshooting for the PanelView Plus 6 terminal involves checking the power supply, communication connections, and software configuration. The user manual and technical data documentation provide detailed information on troubleshooting steps and potential issues that may arise during operation.
Programming
- Programming Software: The PanelView Plus 6 terminal is programmed using FactoryTalk View Studio for Machine Edition software, which allows for the development of custom applications and user interfaces.
- Programming Language: The programming language used for the PanelView Plus 6 terminal is not explicitly mentioned in the provided documentation, but it likely supports standard programming languages such as C, C++, or Python, which are commonly used in industrial automation applications.
Alarm and Error Codes
Alarm and Error Codes: The alarm and error codes for the PanelView Plus 6 terminal are not explicitly mentioned in the provided documentation. However, they are likely to be detailed in the user manual and technical data documentation, which provide information on troubleshooting and error handling.
Additional Resources
Additional Resources: The PanelView Plus 6 terminal has a wide range of resources available, including user manuals, technical data, and catalog number conversions. These resources can be accessed through the Rockwell Automation website or through the Technical Documentation Center.