The Allen-Bradley 150-F43NBDB is a sophisticated soft-starter from the esteemed SMC Flex series, designed for optimal control and protection of 3-phase AC motors. Equipped with a dynamic range of features, this device seamlessly facilitates smooth motor start and stop functions with options like Soft Start, Full Voltage Start, and Smart Motor Braking. Its robust design is complemented by an integrated LCD and keypad for straightforward local configuration, and it supports a comprehensive metering function for accurate energy monitoring. Operating within a 200-460VAC input voltage range and a frequency of 50/60Hz, it boasts a 43 Ampere current rating and 30 HP capacity, making it suitable for diverse industrial applications. The internal bypass contact minimizes heat, allowing for a reduced enclosure size, while its electronic motor overload protection and network I/O capabilities ensure comprehensive safety and efficiency standards.
Go to product
Technical specifications for 150-F43NBDB
Manufacturer | Rockwell Automation |
---|---|
Input Line Voltage | 200-460 VAC |
Enclosure Type | Open |
Part Number/Catalog No. | 150-F43NBDB |
Control Voltage | 100-240 VAC |
Brand | Allen-Bradley |
Product Series | SMC Flex |
Product Description | Smart Motor Controller (SMC) |
Input frequency | 50 / 60 Hz |
Output Current | 43 A |
Output Power | 30 HP |
Supported functions | Soft Start; Selectable kickstart; Current limit start; Dual ramp start, Full Voltage start, Preset Low Speed, Cost-to-rest; Soft Stop and Smart Motor Braking |
Optional functions | Pump control |
Mounting | Panel Mount |
Compatible motor | standard squirrel-cage induction motor or a Wye-Delta, six-lead motor |
Metering function | included |
Manufacturer: | Rockwell Automation |
Operating Modes: | Soft Start, Kickstart, Current Limit, Pump, Control, Dual ramp start, Full Voltage Start, Coast, Soft Stop and Smart Motor Braking. |
Product Line | SMC-Flex |
Brand: | Allen-Bradley |
Kickstart adjustments: | 0, 0.5, 1.0, or 1.5 s @ 450% Full Load Current (FLA) |
Bulletin Number | Solid State Controller |
Product Family: | SMC Flex Smart Motor Controller |
Start-time adjustments: | 2, 5, 10, 15, 20, 25, or 30 s |
Bulletin Number: | 150 |
Current Limit: | 150%, 250%, 350%, and 450% of full load current |
Controller Rating | 480A, 400 HP at 460V AC |
Catalog number: | 150-F43NBDB |
Line Voltage: | 208…460V AC, 3-Phase,47 and 63 Hz |
Operating Modes: | Soft-start, Linear Acceleration/Deceleration, Current Limit, Dual Ramp Start, Full Voltage, Soft Stop, Preset Slow Speed |
Output current | 12-60 Amperes for line-connected motors; 14.9 - 74 Amperes for Delta connected motors |
Optional control mode: | Pump Control |
Output Power | 10 - 30 HP @ 60 Hz; 11 - 22 kW @ 50 Hz for line-connected motors; 20 - 50 HP @ 60 Hz; 22 - 37 kW @ 50 Hz for Delta connected motors |
Rated Voltage | 500/575V AC |
Applicable Motor Type | Standard squirrel-cage induction motor or a Wye- Delta, six-lead motor |
Output contacts | One (1) Normally Open (N.O.); One (1) Normally Closed (N.C.) contacts |
Control Option | Pump |
Line Voltage: | 200…460V AC, 3-Phase, 50 and 60 Hz |
Alarm Contact assignments | Overload, underload, undervoltage, overvoltage, unbalance, jam, stall, and ground fault |
Control Voltage: | 100-1240 VAC |
Selectable Overload Trip Class | Trip Class 10, 15, or 20 |
Output Current range: | Line-Connected Motors: 8.6-43 Amperes Delta Connected Motors: 14.9-74 Amperes |
Metering | Amps, volts, kW, kWh, MW, MWH, elapsed time, power factor, and motor thermal capacity usage. |
Output power range: | Line Connected motors: 10-30 HP; 11-22 kW Delta connected motors: 22-37 kW; 20-50 Hp |
Built-in status indicator | Stopped, starting, stopping, at speed, alarm, and fault. |
Auxiliary Contacts | Four (4) Fully-programmable contacts |
Mounting: | Panel Mount |
Human Interface Module | Integrated |
Communication ports | One (1) DPI for optional HMI; One (1) DPI for expansion module |
Metering | Amps, volts, kW, kWh, MW, MWH, elapsed time, power factor, motor thermal capacity usage |
Status Indication | Stopped, starting, stopping, at speed, alarm, and fault. |
Protection and Diagnostics | Power loss, line fault, voltage unbalance, excessive starts/hour, phase reversal, undervoltage, overvoltage, controller temp, stall, jam, open gate, overload, underload, communication fault. |
Rockwell Disclaimer: The product is used surplus. DO Supply is not an authorized surplus dealer or affiliate
for the Manufacturer of this product. The product may have older date codes or be an older series than that available direct
from the factory or authorized dealers. Because DO Supply is not an authorized distributor of this product, the Original
Manufacturer's warranty does not apply. While many Allen-Bradley PLC products will have firmware already installed, DO
Supply makes no representation as to whether a PLC product will or will not have firmware and, if it does have firmware,
whether the firmware is the revision level that you need for your application. DO Supply also makes no representations
as to your ability or right to download or otherwise obtain firmware for the product from Rockwell, its distributors, or
any other source. DO Supply also makes no representations as to your right to install any such firmware on the product.
DO Supply will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User
License Agreement or similar document related to obtaining or installing firmware.