The Rockwell Automation 150-F625NBAB is a SMC Flex Smart Motor Controller designed for soft starting and reversing of three-phase induction motors. It is a part of the Allen-Bradley series and is used in various industrial applications where precise motor control is required.
Technical Specifications
- Voltage Type for Actuating: AC
- Rated Operating Voltage (Ue): 200 V
- Rated Control Supply Voltage at AC 50 Hz: 230 V
- Rated Control Supply Voltage at AC 60 Hz: 230 V
- Overload Current for Line Connected Devices: 208 A
- Overload Current for Delta Connected Devices: 283 A
- Controller Type: Soft Starter
- Control Options: None
- Trip Classes: 10, 15, 20, and 30
- Trip Current Rating: 117% of motor FLC
- Heatsink Fan Rating: 150VA @ 110/120V AC or 220/240V AC
- DV/DT Protection: RC snubber network for power circuit
- Repetitive Peak Inverse Voltage Rating: 1400V per UL/CSA/NEMA for power circuit
- Operating Frequency: 50/60 Hz for power circuit
- Line Connected Motor Power, Max: 800 Hp @ 600V AC, 60 Hz, 3-phase
- Delta Connected Motor Power, Max: 900 Hp @ 575V AC, 60 Hz, 3-phase
- Rated Impulse Voltage: 6000V per IEC for power circuit
- Dielectric Withstand: 2500V per IEC for power circuit
- Line Connected Motor Current: 208...625 A @ 600/Y/690V AC, 3-phase
- Delta Connected Motor Current: 283...850 A @ 500/575V AC, 3-phase
- Ampere Tested European Style, Max: 6, 6URD33xxx1400 @ 690V for maximum FLC
- Ampere Tested North American Style, Max: A070URD33xxx1400 @ 690V for maximum FLC
- Transient Protection: Metal oxide varistors: 220 Joules (optional) for power circuit
- Insulation Voltage: Rated 500V per IEC for power circuit
- Rated Operational Voltage: 200...480V AC (-15%, +10%) per UL/CSA/NEMA for power circuit
- Input OFF-state Current: <10 mA AC, <3 mA DC for control circuit @ input OFF-state voltage
- Short-circuit Protection Device List: Standard fuse, circuit breaker, and high capacity time delay class CC/J/L
- Number of Contacts: 1 for auxiliary contacts
- Contact Type: Auxiliary contacts 19/20 (Aux #1), 29/30 (Aux #2), 31/32 (Aux #3), and 33/34 (Aux #4)
Environmental Conditions
- Steady State Heat Dissipation with Control and Fan Power: 446 W
- Storage and Transportation Temperature: -20 °C
- Humidity: 5...95% (noncondensing)
- Operating Temperature: Open: -5 to 50 °C (23 to 122 °F)
- Protection against Electrical...: Not specified
User Manuals and Troubleshooting
The user manual for this product is not directly available from our research. However, the technical specifications and environmental conditions are detailed, which can be useful for troubleshooting and understanding the product's capabilities.
Programming
The programming details for this product are not directly available from our research. However, the technical specifications and environmental conditions are detailed, which can be useful for understanding the product's capabilities and potential programming requirements.
Installation
The installation details for this product are not directly available from our research. However, the technical specifications and environmental conditions are detailed, which can be useful for understanding the product's capabilities and potential installation requirements.
Replacement Part Numbers
our research include a list of replacement part numbers for bypass contactors used with SMC-3 and SMC Flex soft starters, including the 150-F625NBA.
Availability
The product is listed as out of stock on the CBT Company website.
Go to product